SN Query

Language

HomeElevator Control EVC-ICC-A5
Parameter Settings
Main

The system and software information:

image.png

Network

image.png

Network Settings:

DHCP: enable / disable DHCP function

IP: IP address should be unique in the same network

Mask: according to the actual network situation

Gateway: according to the actual network situation

DNS: according to the actual network situation

Click the submit button to complete parameter modification:

Device

image.png

Lift control device settings:

Build: Building number of EVC ( the same with the outdoor panel which is used

together.),range 1~999

Riser: Unit number of EVC,range 0~99

Device Address: range 0~98

Click the submit button to complete parameter modification:

Settings

image.png

Lift control Settings:

Mode: Working mode EVRC or EVDC

EVRC:Usually used to control the internal call panel of elevator

Use contacts:Choose the type of contacts

Type:Control down and up key of lift’s external call panel,or only control down key

of lift’s external call panel

Relay time:The default time is 500ms,which is used to stimulate the time of

pressing up and down key.

EVDC:Usually used to control the external panel of elevator

Select the EVRC/EVDC mode and click the submit button, the corresponding parameter

setting interface will appear.

Use contacts:Choose the type of contacts

Type:Control Automatically or Control Manually

Use:Configure the settings based on Floor and Apartment

Lift release time (card):The duration of triggering with card

Lift release time (intercom): The duration of triggering via intercom

Energise all relays(FailSafe):if you want the relay status to be opposite when

power it,enable it,if not,leave it alone. (Usage: On EVRC mode of the elevator

module, when you enable this option, you can use the NC port of the relays as an NO

port to connect the Floor buttons inside the elevator. In this way, the module in the

case of failure or power will not affect the normal use of the elevator.)


8.4.1 EVRC mode

Lift release time (card): 0~9999 (default 5s)seconds

Lift release time (intercom):0~9999 (default 1s)seconds

use Contacts COM/NO:When receiving the corresponding trigger command, the

normally-open (NO) relay will activate.

use Contacts COM/NC:When receiving the corresponding trigger command, the

normally-closed (NC) relay will activate.

Type:Control Automatically or Control Manually

Use:Configure the settings based on Floor and Apartment

Energise all relays(FailSafe):

When EVC enables this function, all relays are in the opposite state.

When EVC is Powered on with this function enabled,all relays are in the opposite

state. use Contacts COM/NO:When receiving the corresponding trigger command, the

normally-closed (NC) relay will activate.

use Contacts COM/NC:When receiving the corresponding trigger command, the

normally-open (NO) relay will activate.

The relay will be restored to its original state after Power OFF.

If “Use” at “Settings” is configured as “Floor”,you will see “Advanced” as follow:

image.png

If“Use”at “Settings”is configured as“Apartment”,you will see “Advanced "as follow:

image.png

When“Type” is configured as“Automatic”,the table will display as follow. In this

configuration,the two relays at lift controller will be triggered at the same time,B1 and

B9,B2 and B10,B3 and B11…will be triggered in pairs at the same time.

image.png

Select button: Setting Upload File Path

Import: After setting the file path, click Import to upload the file.Only support “.csv”format file.

image.png

Export: Export configuration file (.csv)

Port: Select port 1~16(B1~B16)

Floor/Apartment: Support 1 to 4 digits that is the same as the indoor monitor’s room

number

For Example:

Indoor Monitor

IP Address: 192.168.98.190

Building Number: 1

Unit: 1

Room: 101

Device: 0

image.png

Outdoor Panel:

IP Address: 192.168.98.54

Building: 1

Unit: 1

image.png

EVC Module:

IP Address:192.168.98.231

Building:1

Riser(Unit):1

image.png

when“Type” is configured as“Manual”,the EVC relay Port1 (B1) normally-open contact

will work,and visitors can press the floor button he want to visit,in this example,he will

have access to press floor 1;When“Type“ is configured as“Automatic”, the EVC relay

Port1 (B1) and Port9 (B9) normally-open contact will work at the same time,vistors no

need to do any operation.

Permit button: Permission to open the floor where the indoor monitor is located

image.png

8.4.2 EVDC mode(Type: only control Down Button of elevator )

image.png

image.png

Parameter settings are the same as EVRC.

Click indoor monitor Elevator icon(only Down button enable) , the EVC relay Port1 (B1)

normally-open contact will work.

image.png

8.4.3 EVDC mode(Type: control UP & Down Buttons of elevator )

image.png

image.png

Parameter settings are the same as EVRC.

Click indoor monitor Elevator icon(Down button) , the EVC relay Port1 (B1) normally-

open contact will work.

Click indoor monitor Elevator icon(UP button) , the EVC relay Port9 (B9) normally-open

contact will work.

Note:

Port 1(B1) corresponds to port 9(B9)

Port 2(B2) corresponds to port 10(B10)

Port 3(B3) corresponds to port 11(B11)

Port 4(B4) corresponds to port 12(B12)

Port 5(B5) corresponds to port 13(B13)

Port 6(B6) corresponds to port 14(B14)

image.png

Card

image.png

The controller supports to connect with a card reader via RS485 to realize that the residents can swipe their fobs at lift car to call the lift/elevator,and the controller will provide access to the floor where the fobs are bound with.

You can Export and Import the card list here,and also Add the fobs/cards here manually and automatically.

If you want to Add the fobs/cards automatically,pls make sure the controller and card reader is connected correctly,and then press “Start read” to start reading card No.,swipe the fob/card above card reader,a card adding interface will come out automatically,you can only input apartment No.,then press “Add” to add this card to the card list.

image.png

Note:1. The card list only works at “EVRC” mode.

2.Make sure the RS485 port is existing at the controller,because some old version doesnot support RS485 now,because some components are not patched before.


Logout

image.png

Prev Next